Smooth-ceiling geometry
The layout keeps detector-to-detector spacing within the applicable spacing and checks every grid-cell corner against the maximum radius.
R = 0.7 × S
BAS Software SolutionsTechnical workflow software

NFPA 72 planning assistant
Enter the room, ceiling, detector, and adopted-edition information. The calculator identifies the rule path, computes a conservative rectangular layout, and shows every suggested detector coordinate.
Required inputs
NFPA 72 directs line-type integration detectors to the manufacturer's published instructions. A prescriptive grid is not calculated.
Prescriptive layout available
Diagram is proportional; dimensions govern.
Coordinates are measured from the lower-left corner of the entered rectangle.
How the calculator works
The layout keeps detector-to-detector spacing within the applicable spacing and checks every grid-cell corner against the maximum radius.
R = 0.7 × S
Spot-type listed spacing is multiplied by the NFPA 72 ceiling-height factor. The 0.4H floor is applied where it permits a larger value.
Sₐ = max(S × factor, 0.4H)
The chosen edition is carried into the rule path and printout. Confirm the adopted edition and the heat detector listing before using the result.
Edition + device + ceiling → rule set