Equation guide
How pressure switch deadband is calculated
Switch deadband—also called differential—is the separation between the trip point and the reset point. It prevents rapid cycling when the process hovers near the set point. The required reset direction depends on whether the switch trips on a rising or falling process.
This tool evaluates both the numerical deadband and the physical operating direction. A small numerical difference cannot pass if the reset occurs on the wrong side of the trip point.
Deadband in engineering units
Deadband = |Trip point − Reset point|The absolute value reports a positive differential in PSI, inH₂O, temperature, level, or the selected process unit.
Deadband as percent of span
Deadband % = Deadband ÷ (URV − LRV) × 100Use the calibrated range, not the trip point, when the specification is stated as percent of span.
Maximum allowed deadband
Maximum = Span × Allowed % ÷ 100When the specification is fixed in engineering units, the entered maximum is used without conversion.
Direction check
High-acting: Reset < Trip | Low-acting: Reset > TripFinal pass requires the proper reset direction and an observed deadband at or below the maximum.
Worked example: high-acting pressure switch
A 0–100 PSI switch trips at 75 PSI and resets at 72 PSI. Its maximum allowed deadband is 5% of span.
Switch deadband FAQs
Are deadband and hysteresis the same?
In many field procedures the terms are used interchangeably for the difference between operate and reset points. Manufacturer terminology can vary, so follow the device data sheet and approved procedure.
Why must a high-acting switch reset below its trip point?
After tripping on a rising input, the process must fall far enough to cross the separate reset threshold. The opposite relationship applies to a low-acting switch.
Should I use percent of range or percent of set point?
Use the exact basis stated in the specification. This calculator’s percent option is percent of calibrated span; choose fixed engineering units when the manufacturer provides a fixed differential.
Does this test prove the complete switch loop works?
No. A complete functional test may also require contact verification, control-system indication, alarm or trip action, wiring checks, and documentation under the applicable procedure.